Customer Response System


Ticket Number: 20190611-82119
Tech is currently away, call 401-942-8000 for immediate assistance


Response from Ben Needham:
Ok so,

Assuming the pump was sized based off of a design flow of approximately 1GPM...

The head loss in your system would be ~ 0.5Ft

If I plot out your system curve overlaid with the 007 pump curve, the actual expected flow would be ~ 4GPM

40 feet of 3/4 inch type L copper will hold ~ 1.016 Gallons

1.016Gal/(4 Gal/Min) ~ apprximitly 15 Seconds

Provided the assumptions are correct.


Your Response:


Add Attachments (PNG, JPG, and PDF only)




Tech Support Hours

8:00 am -5:00 pm | Monday - Friday
401-942-8000
Show holiday list

All submissions received after 4:30 pm on a Friday or holiday will be answered on Monday or the next available business day.
Message Log

    Response from Customer
      Posted By: on 2021-03-31 13:53:53
      Message:

    Response from Customer
      Posted By: on 2021-01-22 03:58:52
      Message:

    Response from Customer
      Posted By: on 2020-11-23 10:32:41
      Message:

    Response from Customer
      Posted By: on 2020-11-06 01:51:55
      Message:

    Response from Customer
      Posted By: on 2020-11-03 01:54:20
      Message:

    Response from Customer
      Posted By: on 2020-10-19 15:30:46
      Message:

    Response from Taco
      Posted By: Ben Needham on 2019-06-12 10:20:39
      Message: Ok so, Assuming the pump was sized based off of a design flow of approximately 1GPM... The head loss in your system would be ~ 0.5Ft If I plot out your system curve overlaid with the 007 pump curve, the actual expected flow would be ~ 4GPM 40 feet of 3/4 inch type L copper will hold ~ 1.016 Gallons 1.016Gal/(4 Gal/Min) ~ apprximitly 15 Seconds Provided the assumptions are correct.

    Response from Customer
      Posted By: Brian Davis on 2019-06-11 13:57:28
      Message: Hi Ben, 3/4'' copper pipe 40' determined length to the fixture Thanks , Brian

    Response from Taco
      Posted By: Ben Needham on 2019-06-11 13:27:12
      Message: Hi Brian, What is the length of pipe and diameter to the fixture? Thanks, Ben

    Original Message:
      taco 007 connected to bottom of 40 gallon water heater, total length of circ loop is 80' back to wh, connects at top of incoming cold.
      piping is 3/4 l copper. city water pressure is 55psi
      pump is controlled with switch at sink
      how long will it take for the pump to deliver hot water to the sink,when the pump is activated?


      thank you for your assistance
      bdavis280@yahoo.com